E&I Field Calculators

Quick reference calculators for electrical, instrumentation, controls, pipe flow, and industrial field-service work.

GPM to FPS / Pipe Velocity Calculator

Formula: Velocity ft/s = 0.4085 × GPM ÷ inside diameter²

Velocity —
Pipe Area —

4-20 mA Scaling Calculator

Enter the mA signal, low range value, and high range value.

Scaled Process Value —
Percent of Span —

Ohm’s Law Calculator

Enter voltage and current to calculate watts and resistance.

Power —
Resistance —

Voltage Drop Calculator

Basic single-phase/DC voltage drop estimate using conductor resistance per 1000 ft.

Voltage Drop —
Voltage Drop Percentage —

Basic Conduit Fill Percentage Calculator

Use actual conduit internal area and conductor area from approved tables or manufacturer data.

Total Conductor Area —
Calculated Fill —
Target Comparison —

Metric Prefix Converter

Convert between pico, nano, micro, milli, base units, kilo, mega, and giga.

Converted Value —
Base Unit Value —

These calculators are provided for general field reference only. Verify all calculations using applicable codes, project specifications, manufacturer documentation, engineering requirements, and approved installation standards.

Motor Cable Ampacity & Overload Calculator

Estimate motor branch-circuit conductor ampacity, suggested conductor size using the 75°C ampacity column, and motor overload protection settings.

Motor Conductor Sizing

For conductor sizing, use the applicable NEC motor FLC table value and multiply by 125%. This is separate from overload protection. Motor conductor sizing is generally based on the NEC motor FLC value, not necessarily the motor nameplate FLA.

Minimum Required Conductor Ampacity —
Suggested Minimum Conductor Size, 75°C Column —
Adjusted Conductor Ampacity —

Motor Overload Protection

For overload protection, use the motor nameplate FLA. Motors with a service factor of 1.15 or greater, or a temperature rise of 40°C or less, are commonly sized at 125% of nameplate FLA. Other motors are commonly sized at 115% of nameplate FLA.

Maximum Overload Setting —
Overload Percentage Used —

Field Notes

Do not confuse motor conductor sizing, motor overload protection, and breaker or fuse sizing. They are related but separate calculations.

  • Motor conductor sizing: commonly based on applicable NEC motor FLC × 125%.
  • Motor overload sizing: commonly based on motor nameplate FLA × 115% or 125%.
  • Service factor note: if service factor is 1.15 or greater, or temperature rise is 40°C or less, overload sizing commonly uses 125% of nameplate FLA.
  • Other motors: commonly use 115% of nameplate FLA for overload sizing.
  • Breaker/fuse sizing: short-circuit and ground-fault protection is a separate motor calculation.
  • 75°C column: this calculator uses common 75°C ampacity values for copper and aluminum conductors.
  • Adjustment factors: use the correct adjustment/correction factors for the actual installation conditions.

Important: This calculator is for general field reference only. Verify motor conductor sizing, overload protection, short-circuit and ground-fault protection, temperature correction, adjustment factors, terminal ratings, local amendments, AHJ requirements, and project specifications using the currently adopted NEC and approved documentation.